Revenue grade power meter with data logging capabilites for single and three phase circuits features integrated on-board LCD display, field selectable 5 A or 1 A input for current transformers and wide range AC power supply input.
Revenue grade power meter with data logging capabilites for single and three phase circuits features integrated on-board LCD display, field selectable 5 A or 1 A input for current transformers and wide range AC power supply input.
| Accuracy Acuvim-II | Accuracy Acuvim-IIR/IIE/IIW | Resolution | Range | |
| Voltage | 0.2% | 0.2% | 0.1V | 20V~1000kV |
| Current | 0.2% | 0.2% | 0.1mA | 5mA~50000A |
| Power | 0.5% | 0.2% | 1W | -9999MW~9999MW |
| Reactive Power | 0.5% | 0.2% | 1var | 9999Mvar~9999Mvar |
| Apparent Power | 0.5% | 0.2% | 1VA | 0~9999MVA |
| Power Demand | 0.5% | 0.2% | 1W | -9999MW~9999MW |
| Reactive Power Demand | 0.5% | 0.2% | 1var | -9999Mvar~9999Mvar |
| Apparent Power Demand | 0.5% | 0.2% | 0.2% | 0~9999MVA |
| Power Factor | 0.5% | 0.2% | 0.001 | -1.000~1.000 |
| Frequency | 0.2% | 0.2% | 0.01Hz | 45.00~65.00Hz |
| Energy Primary | 0.5% | 0.2% | 0.1kWh | 0-99999999.9kWh |
| Energy Secondary | 0.5% | 0.2% | 0.001kWh | 0-999999.999kWh |
| Reactive Energy Primary | 0.5% | 0.2% | 0.1kvarh | 0-99999999.9kvarh |
| Reactive Energy Secondary | 0.5% | 0.2% | 0.001kvarh | 0-999999.999kvarh |
| Apparent Energy Primary | 0.5% | 0.2% | 0.1kVAh | 0-99999999.9kVAh |
| Apparent Energy Secondary | 0.5% | 0.2% | 0.001kVAh | 0-999999.999kVAh |
| Harmonics | 1.0% | 1.0% | 0.1% | 0.0%~100.0% 20.0%~100.0% (IIR/IIE/IIW) |
| Phase Angle | 2.0% | 2.0% | 0.1° | 0.0°~359.9° |
| Unbalance Factor | 2.0% | 2.0% | 0.1% | 0.0%~100.0% |
| Running Time | 0.01h | 0~9999999.99h |
| Current Inputs (Each Channel) | ||||
| Nominal Current | 5A /1A | |||
| Metering Range | 0~10A AC | |||
| Withstand | 20Arms continuous, 100Arms for 1 second, non-recurring | |||
| Burden | 0.05VA (typical) @ 5Arms | |||
| Pickup Current | 0.1% of nominal | |||
| Accuracy | 0.2% full scale | |||
| Voltage Inputs (Each Channel) | ||||
| Nominal Full Scale | 400V AC L-N, 690V AC L-L (+20%) | |||
| Withstand | 1500V AC continuous 2500V AC, 50/60Hz for 1 minute | |||
| Input Impedance | 2Mohm per phase | |||
| Metering Frequency | 45Hz~65Hz | |||
| Pickup Voltage | 10V AC (30V AC for Acuvim IIR/IIE/IIW) | |||
| Accuracy | 0.2% full scale | |||
| Energy Accuracy (Acuvim IIR/IIE/IIW) | ||||
| Active | According to IEC 62053-22: Class 0.2s According to ANSI C12.20: Class 0.2s | |||
| Reactive (according to IEC 62053-23) | Class 2 | |||
| Harmonic Resolution | ||||
| Metered Value | Acuvim II: 31st harmonic Acuvim IIR/IIE/IIW: 63rd harmonic | |||
| Control Power | ||||
| Universal | AC or DC | |||
| Operating Range | 100~415V AC, 50/60Hz 100~300V DC | |||
| Burden | 5W | |||
| Frequency | 50/60Hz | |||
| Withstand | 3250V AC, 50/60Hz for 1 minute Installation Category III (Distribution) | |||
| Low Voltage DC Control Power (Optional) | ||||
| Operating Range | 20~60V DC | |||
| Burden | 5W | |||