The single-circuit energy meter provides a basic energy metering solution for a wide variety of applications including tenant submetering, tenant billing and cost allocation. Simple pulse outputs communicate real and reactive energy.
The single-circuit energy meter provides a basic energy metering solution for a wide variety of applications including tenant submetering, tenant billing and cost allocation. Simple pulse outputs communicate real and reactive energy.
Discontinued!
This product has been discontinued and is no longer available. There are no replacement options.
We can help you find what you need:
The single-circuit energy meter provides a basic energy metering solution for a wide variety of applications including tenant submetering, tenant billing and cost allocation. Simple pulse outputs communicate real and reactive energy.
Features
Applications
| Real Power and Energy | 0.5% (ANSI C12.20, IEC 62053-22 Class 0.5S) |
| Control Power, AC | 50/60 Hz; 5 VA max.; 90 V min.; UL Maximums: 600 VL-L (347 VL-N); CE Maximum: 300 VL-N |
| Control Power, DC | 3 W max.; UL and CE: 125 to 300 VDC (external DC current limiting required) |
| Voltage Input | UL: 90 V L-N to 600 V L-L; CE: 90 V L-N to 300 V L-N |
| Current Input | 50 to 5,000 A |
| Scaling Input Range | E683x series rope-style CTs only (CTs must be rated for connection to Class 1 voltage inputs) |
| Operating Temperature Range | -22 to 158°F (-30 to 70°C) |
| Storage Temperature Range | -40 to 185°F (-40 to 85°C) |
| Humidity Range | <95% RH non-condensing |
| Mounting Location | Not suitable for wet locations; for indoor use only |
| Warranty | 5 years limited |
| Agency Approvals | UL 508, IEC/EN 61010-1, California CSI Solar, ANSI C12.20 |
| Real Power and Energy | 0.5% (ANSI C12.20, IEC 62053-22 Class 0.5S) |
| Control Power, AC | 50/60 Hz; 5 VA max.; 90 V min.; UL Maximums: 600 VL-L (347 VL-N); CE Maximum: 300 VL-N |
| Control Power, DC | 3 W max.; UL and CE: 125 to 300 VDC (external DC current limiting required) |
| Voltage Input | UL: 90 V L-N to 600 V L-L; CE: 90 V L-N to 300 V L-N |
| Current Input | 50 to 5,000 A |
| Scaling Input Range | E683x series rope-style CTs only (CTs must be rated for connection to Class 1 voltage inputs) |
| Operating Temperature Range | -22 to 158°F (-30 to 70°C) |
| Storage Temperature Range | -40 to 185°F (-40 to 85°C) |
| Humidity Range | <95% RH non-condensing |
| Mounting Location | Not suitable for wet locations; for indoor use only |
| Warranty | 5 years limited |
| Agency Approvals | UL 508, IEC/EN 61010-1, California CSI Solar, ANSI C12.20 |