Kyoritsu 6310-07 Power Quality Analyzer with Load current clamp sensor Model 8127 100A x 3
- Can measure Flicker in accordance to IEC 61000-4-15 and EN50160 standards. Using our Flicker sensor, available as optional accessory, Pst value (short term severity in 10 minutes value) and the Plt value (long term severity in 2 hours value) can be measured.
- 12 kinds of Power Measurements for Power Control and Applicable to Power Quality Control including Harmonics Analysis.
- One click easy-to-use operation helps complicated setting and processing of large data through the setting / analyzing software provided as accessory.
- Direct communication with PC via USB cable
- Built-in Input / Output Function of external signal enables the signal transmission to alarms.
- 2-way power supply by AC and Battery, and Nickel hydrogen battery usable with rechargeable function.
- Pull / Insert of CF card possible whenever on recording under the function of memory backup device.
- Can monitor insulation at leakage current by using optional leak clamp sensors.
- Built-in Print Screen Function enables to record display screen
- (Records 512 screens by using CF card: 1 screen 40KB).
- Can display Waveform and Vector, and can confirm the wiring connection, too.
- Complies fully with International Safety Standards IEC 61010-1 CAT.III 600V.
SPECIFICATION:
Wiring connections: 1P 2W, 1P 3W, 3P 3W, 3P 4W
Measurements and parametersVoltage, Current, Frequency, Active power, Reactive power, Apparent power, Active energy, Reactive energy, Apparent energy, Power factor (cos θ), Neutral current, Demand, Harmonics, Quality (Swell/Dip/Instantaneous Stop, Transients/Over Voltage, Inrush Current, Unbalance Rate, IEC Flicker [Pst(1 min)*, Pst, Plt]), Phase Advance Condenser (*Pst can be shown in details for 1 minute intervals.)
Other functionsDigital output function, External communication function, Scaling function
Voltage : Ranges [RMS]: 150 / 300 / 600 /1000V (CF: 2.5 or less, 100% or less of each range) Allowable input : 10~110% of each range (1000V range : 20%~) Display ranges: 5~120% of each range Accuracy : ±0.3%rdg±0.2%f.s. (sine wave, 45~65Hz)
Current : Ranges [RMS]:
- 8128 (50Atype ): 1 / 5 / 10 / 20 / 50A
- 8127 (100Atype ): 10 / 20 / 50 / 100A
- 8126 (200Atype ): 20 / 50 / 100 / 200A
- 8125 (500Atype ): 50 / 100 / 200 / 500A
- 8124 (1000Atype ): 100 / 200 / 500 / 1000A
- 8129 (3000Atype ): 300 / 1000 / 3000A
- (CF: 3.0 or less. 90% or less of each range)
Allowable input10~110% of each range Display ranges1~120% of each range Accuracy ±0.3%rdg±0.2%f.s. + Accuracy of Clamp sensor (sine wave, 45~65Hz)
Activa power accuracy: ±0.3%rdg±0.2%f.s. + Accuracy of Clamp sensor (Power factor 1, Sine wave, 45~65Hz)
Influence of power factor: ±1.0%rdg (reading at power factor 0.5 against power factor 1)
Frequency meter range: 40~70Hz
Display: 320×240 (RGB) Pixel, 3.5-inch color STN display
Temperature & humidity range: 23ºC±5ºC, Relative humidity 85% or less (no condensation)
Storage Temperature & humidity range: -20ºC±60ºC, Relative humidity 85% or less(no condensation)
Operating Temperature & humidity range: 0ºC±40ºC, Relative humidity 85% or less(no condensation)
Power supply: AC 100V ~ 240V±10% (45~65Hz) Alkaline size AA battery LR6 (9V 1.5V × 6) or Ni-MH (HR15-51)
Dimension: 175(L)×120(W)×68(D) mm
Weight: approx. 900g (including batteries)