The RoCoil flexible current transformer is designed for accurate nonintrusive measurement of AC current, pulsed DC or distorted waveforms where conventional rigid core sensors are unsuitable and may be used to measure AC current over a wide dynamic range and from 20 Hz to 5 kHz with 15 m leads.

The RoCoil flexible current transformer is designed for accurate nonintrusive measurement of AC current, pulsed DC or distorted waveforms where conventional rigid core sensors are unsuitable and may be used to measure AC current over a wide dynamic range and from 20 Hz to 5 kHz with 15 m leads.

Your Price $180.00 USD
Availability 2 to 3 Weeks
Quantity

Add In-House Traceable Calibration to your CTR16A4U-15M

Add In-House Traceable Calibration to your CTR16A4U-15M


Dent CTR16A4U-15M Specifications

Sensor Length 16" (40 cm)
Window Size 4.5" (11.5 cm)
Sensor Coil O.D 5.5" (13.9 cm)
Locking Connector O.D. 7.8" (2 cm)
Sensor Coil Diameter 0.47" (1.2 cm)
Output Signal 131 mV/1000A @ 60 Hz
109.2 mV/1000A @ 50 Hz
Current Range 5 - 5000 A AC
Accuracy (typical) <0.6%
Phase Shift <0.2° at 50/60 Hz
Temperature Sensitivity 0.07% per °C
Working Temperature -4 to 158°F (-20 to 70°C)
Working Voltage 1000 Vrms maximum
Dielectric Strength 7400 VAC around coil
1000 VAC rated leads
Certifications Conforms to: UL STD 61010-1
Certified to: CAN/CSA STD C22.2 No. 61010-1
Click here for complete specifications on the Dent CTR16A4U-15M

What's included with the Dent CTR16A4U-15M

  • DENT CTR16A4U-15M RoCoil Flexible Current Transformer, 15 m leads
  • Customer Reviews for the Dent CTR16A4U-15M

    Ask a question about DENT CTR16A4U-15M RoCoil Flexible Current Transformer, 15 m leads

    comments powered by Disqus

    Dent CTR16A4U-15M Specifications

    Sensor Length 16" (40 cm)
    Window Size 4.5" (11.5 cm)
    Sensor Coil O.D 5.5" (13.9 cm)
    Locking Connector O.D. 7.8" (2 cm)
    Sensor Coil Diameter 0.47" (1.2 cm)
    Output Signal 131 mV/1000A @ 60 Hz
    109.2 mV/1000A @ 50 Hz
    Current Range 5 - 5000 A AC
    Accuracy (typical) <0.6%
    Phase Shift <0.2° at 50/60 Hz
    Temperature Sensitivity 0.07% per °C
    Working Temperature -4 to 158°F (-20 to 70°C)
    Working Voltage 1000 Vrms maximum
    Dielectric Strength 7400 VAC around coil
    1000 VAC rated leads
    Certifications Conforms to: UL STD 61010-1
    Certified to: CAN/CSA STD C22.2 No. 61010-1