Designed to meet the most stringent demands in industry and electrical contracting, and meets EN 61010, 600 V CAT III safety standards and is CE marked and UL approved. Features a 0.78" (20 mm) jaw opening and will accommodate conductors up to 250 kcmil, and the unique hooked jaw design facilitates clamping and hooking into conductors.
Designed to meet the most stringent demands in industry and electrical contracting, and meets EN 61010, 600 V CAT III safety standards and is CE marked and UL approved. Features a 0.78" (20 mm) jaw opening and will accommodate conductors up to 250 kcmil, and the unique hooked jaw design facilitates clamping and hooking into conductors.
Features a 0.78" (20 mm) jaw opening and will accommodate conductors up to 250 kcmil, and the unique hooked jaw design facilitates clamping and hooking into conductors. Polycarbonate materials and ultrasonic welding are used throughout to ensure ruggedness and overall lasting reliability. Uses a nickel core to improve accuracy and phase shift on the low end of the measurement range. The current probe is an excellent probe to be used in power and low-level current measurement application.
Features
Applications
Range | Nominal: 10 AAC Measurement: 0.1 to 10 AAC |
Transformation Ratio | Voltage output |
Output Signal | 100 mV/A (1 VAC at 10 A) |
Accuracy | 0.1 to 1 A: 1% of reading ±20 mA 1 to 10 A: 1% of reading ±0.15 A |
Phase Shift | 1 to 5 A : ≤1° at 60 Hz 5 to 10 A: ≤1.5° at 60 Hz |
Overload | 20 A continuous |
Frequency Range | 40 Hz to 3 kHz |
Load Impedance | 1 MΩ |
Crest Factor | 3 at 10 Arms with an error (due to CF) of 3% |
Working/Common Mode Voltage | 600 Vrms |
Output Termination | Double-insulated 5' (1.5 m) lead with two 4 mm safety banana plugs |
Temperature | Operating: 14 to 131°F (-10 to 55°C) Storage: -40 to 158°F (-40 to 70°C) |
Operating Relative Humidity | 85% RH without roll-off above 95°F (95°C) |
Material | Polycarbonate UL 94 |
Jaw Opening | 0.83" (21 mm) |
Maximum Conductor Size | 0.78" maximum (20 mm) |
Dimensions | 5.47 x 2 x 1.18" (139 x 51 x 30 mm) |
Weight | 6.5 oz (180 g) |
Electrical Safety | EN/IEC 61010-1 600 V CAT III, EN 61010-2-32, Pollution Degree 2 |
Protection | IP40 |
Range | Nominal: 10 AAC Measurement: 0.1 to 10 AAC |
Transformation Ratio | Voltage output |
Output Signal | 100 mV/A (1 VAC at 10 A) |
Accuracy | 0.1 to 1 A: 1% of reading ±20 mA 1 to 10 A: 1% of reading ±0.15 A |
Phase Shift | 1 to 5 A : ≤1° at 60 Hz 5 to 10 A: ≤1.5° at 60 Hz |
Overload | 20 A continuous |
Frequency Range | 40 Hz to 3 kHz |
Load Impedance | 1 MΩ |
Crest Factor | 3 at 10 Arms with an error (due to CF) of 3% |
Working/Common Mode Voltage | 600 Vrms |
Output Termination | Double-insulated 5' (1.5 m) lead with two 4 mm safety banana plugs |
Temperature | Operating: 14 to 131°F (-10 to 55°C) Storage: -40 to 158°F (-40 to 70°C) |
Operating Relative Humidity | 85% RH without roll-off above 95°F (95°C) |
Material | Polycarbonate UL 94 |
Jaw Opening | 0.83" (21 mm) |
Maximum Conductor Size | 0.78" maximum (20 mm) |
Dimensions | 5.47 x 2 x 1.18" (139 x 51 x 30 mm) |
Weight | 6.5 oz (180 g) |
Electrical Safety | EN/IEC 61010-1 600 V CAT III, EN 61010-2-32, Pollution Degree 2 |
Protection | IP40 |