Multifunction, panel mount power and energy meter with integrated on-board LCD display, field selectable 5 A or 1 A input for current transformers and wide range AC power supply input. A natively supported B ACnet-IP protocol (BTL listed) allows communication of building automation and control systems for applications such as heating, ventilating, and air-conditioning control, lighting control, access control, and fire detection systems and their associated equipment.
Multifunction, panel mount power and energy meter with integrated on-board LCD display, field selectable 5 A or 1 A input for current transformers and wide range AC power supply input. A natively supported B ACnet-IP protocol (BTL listed) allows communication of building automation and control systems for applications such as heating, ventilating, and air-conditioning control, lighting control, access control, and fire detection systems and their associated equipment.
Discontinued!
This product has been discontinued and is no longer available.
There is no direct replacement, however we recommend the:
Not what you're looking for? Let’s do a search and help you find what you need.
The Accuenergy Acuvim IIBN has a built-in BACnet communication module specifically designed to monitor and collect real-time revenue-grade electrical data for building control and automation applications. This model includes the Acuvim IIBN basic unit with field selectable 1A or 5A current transformer input, 100 to 415V AC, 100 to 300V DC, 50/60Hz power supply, and an integrated mounting option with LCD display.
Features
Applications
The Acuvim IIBN is specially designed for these applications.
| Current Inputs | |
| Metering Range | Channel 1 (0~10A), Channel 2 (0~2A), Channel 3 (0~1.2A), Channel 4 (0~1.2A), Channel 5 (0~1.2A) |
| Pickup Current | Channel 1 (5mA), Channel 2 (1mA), Channel 3 (5mA), Channel 4 (5mA), Channel 5 (5mA) |
| Withstand | 20Arms Continuous, 0.1% of Nominal, 100Arms for 1 second, Non-Recurring |
| Burden | 0.05VA (Typical) @ 5Arms |
| Accuracy | 0.2% Full Scale |
| Voltage Inputs | |
| Withstand | 1500Vac Continuous, 2500Vac, 50/60Hz for 1 Minute |
| Input Impedance | 2Mohm per Phase |
| Metering Frequency | 45Hz~65Hz, 300Hz ~ 500Hz |
| Pickup Voltage | 10Vac |
| Accuracy | 0.2% Full Scale |
| AC/DC Control Power | |
| Burden | 5W |
| Frequency | 50/60Hz |
| Withstand | 3250Vac, 50/60Hz for 1 minute |
| Burden | 5W |
| Frequency | 50/60Hz |
| Withstand | 3250Vac, 50/60Hz for 1 minute |
| Operating Environment | |
| Relative Humidity | 5% to 95% Non-Condensing |
Click on a category to view a selection of compatible accessories with the Accuenergy Acuvim IIBN-D-5A-P1 B ACnet Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc.
| Current Inputs | |
| Metering Range | Channel 1 (0~10A), Channel 2 (0~2A), Channel 3 (0~1.2A), Channel 4 (0~1.2A), Channel 5 (0~1.2A) |
| Pickup Current | Channel 1 (5mA), Channel 2 (1mA), Channel 3 (5mA), Channel 4 (5mA), Channel 5 (5mA) |
| Withstand | 20Arms Continuous, 0.1% of Nominal, 100Arms for 1 second, Non-Recurring |
| Burden | 0.05VA (Typical) @ 5Arms |
| Accuracy | 0.2% Full Scale |
| Voltage Inputs | |
| Withstand | 1500Vac Continuous, 2500Vac, 50/60Hz for 1 Minute |
| Input Impedance | 2Mohm per Phase |
| Metering Frequency | 45Hz~65Hz, 300Hz ~ 500Hz |
| Pickup Voltage | 10Vac |
| Accuracy | 0.2% Full Scale |
| AC/DC Control Power | |
| Burden | 5W |
| Frequency | 50/60Hz |
| Withstand | 3250Vac, 50/60Hz for 1 minute |
| Burden | 5W |
| Frequency | 50/60Hz |
| Withstand | 3250Vac, 50/60Hz for 1 minute |
| Operating Environment | |
| Relative Humidity | 5% to 95% Non-Condensing |
Click on a category to view a selection of compatible accessories with the Accuenergy Acuvim IIBN-D-5A-P1 B ACnet Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc.