ACCUENERGY ACUVIM-AL-D-60-5A-P1 Multifunction LCD Power Meter 100~415Vac, 50~60Hz, 100~300Vdc
The Accuenergy Acuvim L three-phase multifunction power and energy meter offers you reliability, with features like True-RMS measuring parameters and ANSI and IEC 0,2 Accuracy class. This model includes a 60Hz basic unit without communication, standard mount with LCD display, 5Amp current, and a 100~415Vac, 50~60Hz, 100~300Vdc power supply. With the Modbus TRU protocol, monitored data is easily accessible via a standard RS485 communication port. This energy meter also features 4 Quadrant Energy, Power Quality analysis, and Time of Use data. The Acuvim L is ideal for the metering of distribution feeder, generators, motors, transformers, and more: perfect for use with medium and low voltage systems in a variety of commercial, industrial, and utility applications.
Features:
- True-RMS measuring Parameters
- ANSI and IEC 0.2 Accuracy class
- Power Quality Analysis
- 4 Quadrant Energy
- Measure Individual Harmonics from 2nd to 15th (Acuvim-AL/BL/CL/DL)
- Module Design (Acuvim-DL/EL)
- TOU, 4 Tariffs, 12 Seasons, 14 Schedules (Acuvim-EL)
- Class leading Warranty
Applications:
- Metering of distribution feeders, transformers, generators, capacitor banks and motors
- Medium and low voltage systems
- Commercial, industrial, utility
- Power quality analysis
Specifications
Metering
| Parameters |
Acuvim-L Accuracy |
Acuvim-EL/KL Accuracy |
Resolution |
Range |
| Voltage |
0.5% |
0.5% |
0.1V |
20V~1000kV |
| Current |
0.5% |
0.5% |
0.001A |
0~50000A |
| Current Demand |
0.5% |
0.5% |
0.001A |
0~50000A |
| Power |
1.0% |
0.5% |
1W |
-9999MW~9999MW |
| Reactive Power |
2.0% |
0.5% |
1var |
-9999Mvar~9999Mvar |
| Apparent Power |
1.0% |
0.5% |
0.001V |
0~9999MVA |
| Power Demand |
1.0% |
0.5% |
1W |
-9999MW~9999MW |
| Reactive Power Demand |
2.0% |
0.5% |
1var |
-9999Mvar~9999Mvar |
| Apparent Power Demand |
1.0% |
1VA |
1VA |
0~9999MVA |
| Power Factor |
1.0% |
0.5% |
0.001 |
-1.0~1.0 |
| Frequency |
0.2% |
0.2% |
0.01Hz |
45.00~65.00Hz |
| Energy |
0.5% |
0.5% |
0.1kWh |
0~99999999.9kWh |
| Reactive Energy |
2.0% |
0.5% |
0.1kvarh |
0~99999999.9kvarh |
| Apparent Energy |
1.0% |
0.5% |
0.1VAh |
0~99999999.9kVAh |
| Harmonics |
2.0% |
- |
0.01% |
0~100.0% |
| Running Time |
|
|
0.1hrs |
0~999999999.9hrs |
Communication
| RS-485 (Option) |
| Modbus-RTU Protocol |
| 2-wire connection, Half-duplex, Isolated |
| 1200 to 38400 baud rate |
Input
| Current Inputs (Each Channel) |
| Nominal Current |
5 A ac |
| Metering Range |
0~6 A ac |
| Withstand |
20Arms continuous100Arms for 1 second, non-recurring |
| Burden |
0.05VA (typical) @5Arms |
| Pickup Current |
10Vac |
| Accuracy |
0.5% |
| Voltage Inputs (Each Channel) |
| Nominal Full Scale |
400Vac L-N, 690Vac L-L (+20%) |
| Withstand |
1500Vac continuous2500Vac, 50/60Hz for 1minute |
| Input Impedance |
45Hz~65Hz |
| Pickup Voltage |
10Vac |
| Accuracy |
0.5% |
| Energy Accuracy (Acuvim-EL) |
| Active |
(according to IEC 62053-22) Class 0.5s(according to ANSI C12.20) Class 0.5 |
| Reactive |
(according to IEC 62053-23) Class 2 |
| Harmonic Resolution |
| Metered Value |
2nd ~ 15th harmonics(THD of Acuvim-DL is 2nd to 25th) |
Control Power
| Universal |
AC or DC |
| AC/DC Control Power |
| Operating Range |
100~415Vac, 50/60Hz, 100~300Vdc |
| Burden |
3W |
| Withstand |
3250Vac, 50/60Hz for 1 minute |
| Low Voltage DC Control Power (Optional) |
| Operating Range |
20~60Vdx |
| Burden |
3W |
Digital Output Option
| Digital Output (DO) |
(Photo-MOS) |
| Voltage Range |
0~250Vac/dc |
| Load Current |
100mA (Max) |
| Output Frequency |
25Hz, 50% Duty Ratio |
| Isolation Voltage |
2500V |
Digital Input Option
| Digital Output (DI) |
| Input Voltage Range |
20~250Vac/dc |
| Input Current (Max) |
2mA |
| Start Voltage |
15V |
| Stop Voltage |
5V |
| Pulse Frequency (Max) |
100Hz, 50% Duty Ratio |
| SOE Resolution |
2ms |
Operating Environment
| Operation Temperature |
-25°C to 70°C |
| Storage Temperature |
-40°C to 85°C |
| Relative Humidity |
5% to 95% non-condensing |
| Pollution Degree |
2 |
Standard Compliance
| Product |
| USA |
UL 61010-1 |
| Canada |
cUL 61010-1 |
| Europe |
IEC 61010-1 |
| Emission |
| Radiated/Conducted |
FCC Part 15 Subpart B, Class A |
| Radiated/Conducted |
EN 55011 |
| Harmonic |
IEC 61000-3-2 |
| Voltage Fluctuation |
IEC 50081-2 |
| Radio Interference |
IEC 50081-2 |
| Immunity |
| ESD |
IEC 61000-4-2 |
| Radiated, radio-frequency, electromagnetic field |
IEC 61000-4-3 |
| Electrical fast transient/bust |
IEC 61000-4-4 |
| Surge |
IEC 61000-4-5 |
| Conducted disturbances |
IEC 61000-4-6 |
| Power frequency magnetic field |
IEC 61000-4-8 |
| Voltage dips and interruptions |
IEC 61000-4-11 |
| Generic Immunity Standard for Industrial Environment |
EN 50082-2 |
Click here for complete specifications on the Accuenergy Acuvim-AL-D-5A-P1
What's included with the Accuenergy Acuvim-AL-D-5A-P1
Acuvim-AL-D-5A-P1 Power Meter
Acuvim II Series Comparison
| Function |
Parameter |
Acuvim-AL |
Acuvim-BL |
Acuvim-CL |
Acuvim-DL |
Acuvim-EL |
Acuvim-KL |
| Real Time Metering |
Phase Voltage |
U1, U2, U3 |
|
|
|
|
|
|
| Real Time Metering |
Line Voltage |
U12, U23, U31 |
|
|
|
|
|
|
| Real Time Metering |
Current |
I1, I2, I3, In (Acuvim-KL no neutral current measurement) |
|
|
|
|
|
|
| Real Time Metering |
Power |
P1, P2, P3, Psum |
|
|
|
|
|
|
| Real Time Metering |
Reactive |
Power Q1, Q2, Q3, Qsum |
|
|
|
|
|
|
| Real Time Metering |
Apparent Power |
S1, S2, S3, Ssum |
|
|
|
|
|
|
| Real Time Metering |
Power Factor |
PF1, PF2, PF3, PF |
|
|
|
|
|
|
| Real Time Metering |
Load Nature |
L/C/R |
|
|
|
|
|
|
| Real Time Metering |
Frequency |
F Hz |
|
|
|
|
|
|
| Energy & Demand |
Energy |
Ep_imp, Ep_exp |
|
|
|
|
|
|
| Energy & Demand |
Reactive Energy |
Eq_imp, Eq_exp |
|
|
|
|
|
|
| Energy & Demand |
Apparent Energy |
Es |
|
|
|
|
|
|
| Energy & Demand |
Current Demand |
Dmd_I1,Dmd_I2 Dmd_I3 |
|
|
|
|
|
|
| Energy & Demand |
Power Demand |
Dmd_Psum, Dmd_Qsum, Dmd_Ssum |
|
|
|
|
|
|
| Time of Use |
Energy |
TOU, 4 Tariffs, 12 Seasons, 14 Schedules |
|
|
|
|
|
|
| Power Quality |
Voltage Unbalance |
U_unbl |
|
|
|
|
|
|
| Power Quality |
Current Unbalance |
I_unbl |
Trigger, Manual, DI change, Sag/Dips, Swell, Over Current |
|
|
|
| Power Quality |
Voltage THD |
THD_V1, THD_V2, THD_V3 |
|
|
|
|
|
|
| Power Quality |
Current THD |
THD_I1, THD_I2, THD_I3 |
|
|
|
|
|
|
| Power Quality |
Individual Harmonics |
2nd~15th (Voltage and Current) (Acuvim-DL is from 2nd to 25th) |
|
|
|
|
|
|
| Statistics |
Max Current Demand |
Dmd_I1_max,Dmd_I2 _max,Dmd_I3_max |
|
|
|
|
|
|
| Statistics |
Max Power Demand |
Dmd_Psum_max, Dmd_Qsum_max, Dmd_Ssum_max |
|
|
|
|
|
|
| Statistics |
Max & Min of Voltage |
|
|
|
|
|
|
|
| Statistics |
Max & Min of Current |
|
|
|
|
|
|
|
| Hour |
Running Time |
Hour |
|
|
|
|
|
|
| Hour |
Load Running Time |
Hour |
|
|
|
|
|
|
| I/O |
Energy Pulse Output |
2 DO, configured as pulse output for kWh and kvarh, the
pulse rate and width can be set |
|
|
|
|
|
|
| I/O |
Alarm Output |
|
|
|
|
|
|
|
| Communication |
RS-485 |
Modbus®-RTU Protocol, 1200~38400 baud rate |
|
|
|
|
|
|
| Communication |
Second RS-485 |
Modbus®-RTU Protocol, 1200~38400 baud rate |
|
|
|
Opt |
Opt |
|
| Communication |
Profibus |
PROFIBUS-DP/V0 Protocol |
|
|
|
Opt |
Opt |
|
| Extension I/O |
4DI, 2DO |
SOE, Pulse Counter, Pulse output, Alarm output |
|
|
|
Opt |
Opt |
|