Acuvim-KL-D-5A-P1 Power Meter
Downloads:
datasheet manual


Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter Acuvim-KL-D-5A-P1 Power Meter

Acuvim-KL-D-5A-P1 Power Meter

Model: Acuvim-KL-D-5A-P1

Acuvim-KL Power Meter with MODBUS RS485 output, plus integrated on-board LCD display, 5A input for current transformers and wide-range AC power supply input.

$195.00 USD

5 in Stock

Add In House NIST Traceable Calibration to your ACUVIM-KL-D-5A-P1

Include an Enclosure for the Acuvim L series

Clear selected options



Note

The Acuvim KL was specifically designed to measure basic power (kW, kVA, kVAr) and Energy (kWh, kVAh, kVArh) if you need a meter that also measures Voltage check out the Acuvim AL.

About the Acuvim-KL

For energy and facilities professionals who need a low cost single/three phase non-revenue-grade kWh meter. Available with LCD display or DIN Rail mount transducer (no display). All models include MODBUS RS485 communications

The Acuvim-KL is an excellent, low cost meter for basic power (kW, kVA, kVAr and Energy (kWh, kVAh, kVArh) and Load Run Time. Perfect for basic sub-metering applications.


The Acuvim-L Series

The Acuvim-L series are multifunction power meters manufactured by Accuenergy. It is the ideal choice for monitoring and controlling of power distribution system.

Acuvim-L may be used as a data gathering device for an intelligent Power Distribution System or a Plant Automation System. All monitoring data is available via digital RS485 communication port running Modbus® Protocol.

The quality of the power system is important with increasing use of electronic loads such as computers, ballasts or variable frequency drives. With the Acuvim-L power analysis option, any phase current or voltage can be displayed and the harmonic content calculated. By knowing the harmonic distribution, action can be taken to prevent overheated transformers, motors, capacitors, neutral wires and nuisance breaker trips. Redistribution of the system loading can also be determined.


Those looking for Time of Use (TOU) features should look at the Acuvim-EL instead.


Key Features

Metering

  • Voltage V1, V2, V3, V12, V23, V31
  • Current I1, I2, I3, In
  • Power P1, P2, P3, Psum
  • Reactive Power Q1, Q2, Q3, Qsum
  • Apparent Power S1, S2, S3, Ssum
  • Frequency F
  • Power Factor PF1, PF2, PF3, PF
  • Energy Ep_imp, Ep_exp
  • Reactive Energy Eq_imp, Eq_exp
  • Apparent Energy Es
  • Demand Dmd_I1, Dmd_I2, Dmd_I3, Dmd_P, Dmd_Q, Dmd_S

Monitoring

  • Power Quality (functions not included with the Acuvim-KL)
  • Voltage Harmonics 2nd to 15th and THD( Acuvim-DL is from 2nd to 25th)
  • Current Harmonics 2nd to 15th and THD( Acuvim-DL is from 2nd to 25th)
  • Voltage Unbalance Factor U_unbl (all models excluding the Acuvim-KL)
  • Current Unbalance Factor I_unbl (all models excluding the Acuvim-KL)
  • Max/Min Statistics (all models excluding the Acuvim-KL)
  • Meter Running Time and Load Running Time (Acuvim-DL/EL/KL)

Alarms

Two (2) parameters may be set within a specified time interval. If indicated parameter is over or under its setting limit and persists over the specified time interval, the event will be recorded with time stamps and trigger the alarm DO output. The indicated parameter can be selected from any of the 35 parameters available.

Communication

RS485, industry standard Modbus® RTU protocol; (Only on models CL/DL/EL/KL)
Option the second RS485, Modbus® RTU protocol; or PROFIBUS-DP/V0 (available for the DL/EL Models)
Protocol. (just for Acuvim-DL/EL)

Display

Clear and large character LCD Screen display with white back light; Wide environmental temperature endurance.


Applications

  • Metering of distribution feeders, transformers, generators, capacitor banks and motors.
  • Medium and low voltage systems.
  • Commercial, industrial, utility.
  • Power quality analysis.

Communications Options

Acuvim L Series Communications Options
MODBUS RS485 to USB Adapter
MODBUS RS485 to USB Adapter converts MODBUS data running via RS485 to USB for use on local PC


Acuvim L Series is DIN Rail Mountable

Mounting & Display Options

The Acuvim II Series is available in two mounting options:

Standard with LCD Display

The standard model is ANSI C39.1 Standard Compliant with a small size 96x96 outline.

DIN Rail Mount (Remote LCD Display Optional)

The DIN Rail compatible units are DIN 43700 Standard Compliant. The Acuvim L series also offers an optional Remote LCD display.


Acuvim L Series Typical Wiring

Typical Wiring Setups for the Acuvim L Series

Specifications

Metering
Parameters Acuvim-L Accuracy Acuvim-EL/KL Accuracy Resolution Range
Voltage 0.5% 0.5% 0.1V 20V~1000kV
Current 0.5% 0.5% 0.001A 0~50000A
Current Demand 0.5% 0.5% 0.001A 0~50000A
Power 1.0% 0.5% 1W -9999MW~9999MW
Reactive Power 2.0% 0.5% 1var -9999Mvar~9999Mvar
Apparent Power 1.0% 0.5% 0.001V 0~9999MVA
Power Demand 1.0% 0.5% 1W -9999MW~9999MW
Reactive Power Demand 2.0% 0.5% 1var -9999Mvar~9999Mvar
Apparent Power Demand 1.0% 1VA 1VA 0~9999MVA
Power Factor 1.0% 0.5% 0.001 -1.0~1.0
Frequency 0.2% 0.2% 0.01Hz 45.00~65.00Hz
Energy 0.5% 0.5% 0.1kWh 0~99999999.9kWh
Reactive Energy 2.0% 0.5% 0.1kvarh 0~99999999.9kvarh
Apparent Energy 1.0% 0.5% 0.1VAh 0~99999999.9kVAh
Harmonics 2.0% - 0.01% 0~100.0%
Running Time 0.1hrs 0~999999999.9hrs
Communication
RS-485 (Option)
Modbus-RTU Protocol
2-wire connection, Half-duplex, Isolated
1200 to 38400 baud rate
Input
Current Inputs (Each Channel)
Nominal Current 5 A ac
Metering Range 0~6 A ac
Withstand 20Arms continuous100Arms for 1 second, non-recurring
Burden 0.05VA (typical) @5Arms
Pickup Current 10Vac
Accuracy 0.5%
Voltage Inputs (Each Channel)
Nominal Full Scale 400Vac L-N, 690Vac L-L (+20%)
Withstand 1500Vac continuous2500Vac, 50/60Hz for 1minute
Input Impedance 45Hz~65Hz
Pickup Voltage 10Vac
Accuracy 0.5%
Energy Accuracy (Acuvim-EL)
Active (according to IEC 62053-22) Class 0.5s(according to ANSI C12.20) Class 0.5
Reactive (according to IEC 62053-23) Class 2
Harmonic Resolution
Metered Value 2nd ~ 15th harmonics(THD of Acuvim-DL is 2nd to 25th)
Control Power
Universal AC or DC
AC/DC Control Power
Operating Range 100~415Vac, 50/60Hz, 100~300Vdc
Burden 3W
Withstand 3250Vac, 50/60Hz for 1 minute
Low Voltage DC Control Power (Optional)
Operating Range 20~60Vdx
Burden 3W
Digital Output Option
Digital Output (DO) (Photo-MOS)
Voltage Range 0~250Vac/dc
Load Current 100mA (Max)
Output Frequency 25Hz, 50% Duty Ratio
Isolation Voltage 2500V
Digital Input Option
Digital Output (DI)
Input Voltage Range 20~250Vac/dc
Input Current (Max) 2mA
Start Voltage 15V
Stop Voltage 5V
Pulse Frequency (Max) 100Hz, 50% Duty Ratio
SOE Resolution 2ms
Operating Environment
Operation Temperature -25°C to 70°C
Storage Temperature -40°C to 85°C
Relative Humidity 5% to 95% non-condensing
Pollution Degree 2
Standard Compliance
Product
USA UL 61010-1
Canada cUL 61010-1
Europe IEC 61010-1
Emission
Radiated/Conducted FCC Part 15 Subpart B, Class A
Radiated/Conducted EN 55011
Harmonic IEC 61000-3-2
Voltage Fluctuation IEC 50081-2
Radio Interference IEC 50081-2
Immunity
ESD IEC 61000-4-2
Radiated, radio-frequency, electromagnetic field IEC 61000-4-3
Electrical fast transient/bust IEC 61000-4-4
Surge IEC 61000-4-5
Conducted disturbances IEC 61000-4-6
Power frequency magnetic field IEC 61000-4-8
Voltage dips and interruptions IEC 61000-4-11
Generic Immunity Standard for Industrial Environment EN 50082-2
Click here for complete specifications on the Accuenergy Acuvim-KL-D-5A-P1

Acuvim II Series Comparison

Function Parameter Acuvim-AL Acuvim-BL Acuvim-CL Acuvim-DL Acuvim-EL Acuvim-KL
Real Time Metering Phase Voltage U1, U2, U3
Real Time Metering Line Voltage U12, U23, U31
Real Time Metering Current I1, I2, I3, In (Acuvim-KL no neutral current measurement)
Real Time Metering Power P1, P2, P3, Psum
Real Time Metering Reactive Power Q1, Q2, Q3, Qsum
Real Time Metering Apparent Power S1, S2, S3, Ssum
Real Time Metering Power Factor PF1, PF2, PF3, PF
Real Time Metering Load Nature L/C/R
Real Time Metering Frequency F Hz
Energy & Demand Energy Ep_imp, Ep_exp
Energy & Demand Reactive Energy Eq_imp, Eq_exp
Energy & Demand Apparent Energy Es
Energy & Demand Current Demand Dmd_I1,Dmd_I2 Dmd_I3
Energy & Demand Power Demand Dmd_Psum, Dmd_Qsum, Dmd_Ssum
Time of Use Energy TOU, 4 Tariffs, 12 Seasons, 14 Schedules
Power Quality Voltage Unbalance U_unbl
Power Quality Current Unbalance I_unbl Trigger, Manual, DI change, Sag/Dips, Swell, Over Current
Power Quality Voltage THD THD_V1, THD_V2, THD_V3
Power Quality Current THD THD_I1, THD_I2, THD_I3
Power Quality Individual Harmonics 2nd~15th (Voltage and Current) (Acuvim-DL is from 2nd to 25th)
Statistics Max Current Demand Dmd_I1_max,Dmd_I2 _max,Dmd_I3_max
Statistics Max Power Demand Dmd_Psum_max, Dmd_Qsum_max, Dmd_Ssum_max
Statistics Max & Min of Voltage
Statistics Max & Min of Current
Hour Running Time Hour
Hour Load Running Time Hour
I/O Energy Pulse Output 2 DO, configured as pulse output for kWh and kvarh, the pulse rate and width can be set
I/O Alarm Output
Communication RS-485 Modbus®-RTU Protocol, 1200~38400 baud rate
Communication Second RS-485 Modbus®-RTU Protocol, 1200~38400 baud rate Opt Opt
Communication Profibus PROFIBUS-DP/V0 Protocol Opt Opt
Extension I/O 4DI, 2DO SOE, Pulse Counter, Pulse output, Alarm output Opt Opt

Acuview Software

As the need to better understand power and energy consumption increases, Accuenergy continues to offer a simple and effective software compliment to our metering products. Combining their meters with the Acuview software suite allows Accuenergy to offer one of the most powerful yet cost effective metering and monitoring solutions in the market.

Acuview Software Features

  • Simple setup feature for fast deployment and configuration Accuenergy meters.
  • Remote and real time monitoring of all meter parameters.
  • Dozens of meters can be connected to a single PC.
  • Multiple meters can be displayed and tiled in one window.
  • Real Time Data Logging.
  • Logging of data from the I/O modules (pulses from Water, gas, flow, etc).
  • All data logged into simple and easy to read Excel spreadsheets (.xls, .csv or .txt formats).
  • SmartSum feature provides aggregate Energy & Demand data for an average of the entire system being monitored.

Accessories

Click on a category to view a selection of compatible accessories with the Acuvim-KL-D-5A-P1 Power Meter.

AccuEnergy ACUMESH-K RS485 Network Standalone Transceiver ACUMESH-K 88223
AcuMesh wireless metering solution connects Energy and Power Meters communicating with RS485 wirelessly. AcuMesh is a cost-effective solution that eliminates the need for installation of communication wires. This standalone transceiver is able to connect to any device with an RS485 port running Modbus-RTU protocol, and includes a whip antenna and power supply.
$245.00 USD

Learn More

Ask a question about the Acuvim-KL-D-5A-P1 Power Meter:

comments powered by Disqus

Review the Acuvim-KL-D-5A-P1 Power Meter

" data-description="Acuvim-KL Power Meter with MODBUS RS485 output, plus integrated on-board LCD display, 5A input for current transformers and wide-range AC power supply input.">