Extech 382090 1000A 3-Phase Power Analyzer/Datalogger (60 Hz)
Downloads:
datasheet



Extech 382090 1000A 3-Phase Power Analyzer/Datalogger (60 Hz)

Model: 382090

1000A 3-Phase Power Analyzer/Datalogger (60 Hz) - Four clamps for power measurements on single phase, 3-phase/3-wire or 3-phase/4-wire systems.

Sorry! This product has been discontinued.


The Extech 382090 1000A 3-Phase Power Analyzer/Datalogger (60 Hz) has been discontinued, it has been replaced by the Extech PQ3350-1 3-Phase Power & Harmonics Analyzer

Extech 382090 1000A 3-Phase Power Analyzer/Datalogger

1000A 3-Phase Power Analyzer/Datalogger

Four clamps with simultaneous display

On single phase, 3-phase/3-wire or 3-phase/4-wire systems

Key Features:

  • Large backlighting LCD displays 10 parameters simultaneously (kW, kVAR, kVA, PF plus the voltage and current of the 3 phases)
  • Up to four current probes can be connected to the analyzer
  • Clamp-on True RMS power measurements with software for Harmonics analysis
  • Displays Active Power (kW), Apparent Power (kVA), Reactive Power (kVAR) and Power Factor
  • Current measurements to 1000A and Voltage measurements to 600V
  • kWH, kVARh and kVAh energy measurements
  • Automatically logs up to 20,000 sets of measurements and manually logs up to 99 sets
  • Programmable Start/Stop datalogging times
  • PC interface with Windows® 95/98/NT/2000/ME/XP compatible software for single and three phase voltage/current Waveform display and Harmonic analysis
  • Phase sequence measurements
  • Auto power off with disable feature
  • CAT III-1000V, UL Listed; CE approved; 1yr warranty
General
ACV (True rms)999.9V ±(0.5%rdg+10d)
ACA1000A ±(1%rdg+15d)
Active Power (kW)999.9kW ±(1.5%rdg+20d)
Apparent Power (kVA)999.9kVA ±(1.5%rdg+20d)
Reactive Power (kVAR)999.9kVAR ±(1.5%rdg+20d)
Power Factor-1.000 to +1.000 ±(3%rdg+30d)
Frequency60Hz to 100Hz ±(0.5%rdg+1d)
Phase+90.0°~ 0°~ -90.0° ±3°
Active Power Energy (kWh)0.0kWh to 119.3MWh ±(1.5%rdg+20d)
Apparent Power Energy (kVAh)0.0kVAh to 119.3MVAh ±(1.5%rdg+20d)
Reactive Power Energy (kVARh)0.0kVARh to 119.3MVARh ±(1.5%rdg+20d)
Harmonics1 to 31 (with the software) ±(1.5%rdg+20d)
Datalogging20,000 reading
Dimensions9.25 x 4.5 x 2.1" (235 x 116 x 54mm)
WeightMeter: 25.8oz (730g); Clamp: 11.8oz (333g)
Click here for complete specifications on the Extech 382090

Ask a question about the Extech 382090 1000A 3-Phase Power Analyzer/Datalogger (60 Hz):

comments powered by Disqus

Review the Extech 382090 1000A 3-Phase Power Analyzer/Datalogger (60 Hz)

" data-description="1000A 3-Phase Power Analyzer/Datalogger (60 Hz) - Four clamps for power measurements on single phase, 3-phase/3-wire or 3-phase/4-wire systems.">