Dent CT-SRS-005-U Small Revenue Grade Split Core Current Transformers, 5A
Downloads:
datasheet



Dent CT-SRS-005-U Small Revenue Grade Split Core Current Transformers, 5A

Model: CT-SRS-005-U

Hinged split-core current transformers are designed for Revenue Grade applications that require maximum accuracy and precision.

$90.00 USD

was $100.00

Availability: 3 to 4 Weeks

DENT Instruments CT-SRS-005-U Offers

The superior performance, robust design, and unique shrouded snap, lock & tilt top of the SRS Series CTs make them ideal for field installation in high accuracy current measurement applications such as energy and demand metering, tenant submetering and load surveys.

Standard Features:

  • 5A Revenue Grade Split Core
  • 0.2% of rated current
  • Phase Shift <0.2 degrees
  • UL2808 and CSA C22.2

CT-SHS-0005-U Specifications

Key Specifications
Window Size1.0 cm (0.4”)
Current Range0.05—10A
Output333 mV @ rated current
Accuracy+/‐ 0.5% at 0.5% to 140% of rated current
Electrical
Output333 mV
Phase Shift+/‐ 0.5° at rated current
Frequency Range10 Hz to 10 KHz
Mechanical
Dimensions6.4 x 2.5 x 5.1 cm (2.5 x 1.0 x 2.0”)
PolarityWhite lead is positive
Output Lead2.7 M (8’), twisted pair, 22 AWG
Operating Temperature–20° to 50°C (-4° to 122°F)
Other Features
Window Size1.0 cm (0.4”)
Weight136 g (4.8 oz)
Dielectric Strength5000V around the case, 600V rated leads
Storage TemperatureMaximum 105°C (220°F)
Case ProtectionPlastic ABS/PVS or Epoxy encapsulated housing
Safety
Working Voltage600 Vrms maximum
UL listedCAN/CSA‐C60044‐1‐2007 pts 1 & 2
CE MarkANSI/IEEE C57.13, IEEE C57.13.2
Click here for complete specifications on the Dent CT-SRS-005-U

Ask a question about the Dent CT-SRS-005-U Small Revenue Grade Split Core Current Transformers, 5A:

comments powered by Disqus

Review the Dent CT-SRS-005-U Small Revenue Grade Split Core Current Transformers, 5A

" data-description="Hinged split-core current transformers are designed for Revenue Grade applications that require maximum accuracy and precision.">