Dent CT-R16-A4-U 16 in. RoCoil Flexible CT
Downloads:
datasheet



Dent CT-R16-A4-U 16 in. RoCoil Flexible CT

Model: CT-R16-A4-U | Order No: CTR16A4U

16 inch RoCoil CT designed for accurate non-intrusive measurement of AC current, pulsed DC or distorted waveforms.

$120.00 USD

3 in Stock


Dent RoCoil Flexible 16" Current Transformer

The DENT RoCoil™Current Transformers have been designed for accurate non-intrusive measurement of AC current, pulsed DC or distorted waveforms where conventional rigid core CTs are unsuitable. This type of sensor may be used to measure AC current over a wide dynamic range and from 20 Hz to 5 kHz. Note: Some applications may require use of integrator/amplifier. See also RoCoil mV™.

Key Specifications

Models CT-R16-A4-U CT-R24-A4-U CT-R36-A4-U CT-R47-A4-U
Four Lengths 40 cm (16") 60 cm (24") 90 cm (35") 120 cm (47")
Window Size 11.5 cm (4.5") 17.9 cm (7.0") 27.5 cm (10.8") 37 cm (14.6")
Output Signal (di/dt) 131 mVAC/1000A @ 60 Hz
109.2 mV/1000A @ 50 Hz
Current Range 5 - 5000A AC*
Accuracy (typical) < 0.6%**

General Specifications

Electrical
All accuracies specified at 20°C (±2°C) with RoCoil™ centered on conductor.
Output Signal 131 mV/1000A @ 60 Hz
109.2 mV/1000A @ 50 Hz
Wire Colors White = (+) positive
Brown = (-) negative
Bare wire = shield
Phasing Arrow Points Towards Load
Phase Shift < 0.2° at 50/60 Hz
Frequency Range 20 Hz to 5 kHz*
Useful Current Range 5 - 5000A AC*
Linearity ± 0.2%
Temperature Sensitivity 0.07% per °C
Mechanical
Coil Materials Blue thermoplastic rubber, flame retardant UL 94 V-0 rated
Coupling Materials PA6 UL 94 V-0 rated
Shielding 100% transducer, 100% output lead
Working Temp -20 °C to +70 °C (-4° to +158 °F)
Safety
Working Voltage 1000 Vrms maximum
Dielectric Strength 7400 VAC around coil
1000 VAC rated leads
Certifications Conforms to UL STD 61010-1
Certified to CAN/CSA STD C22.2
No. 61010

*Depending on meter compatibility. RoCoil CTs UL Rated to 100KA AC.
ELITEpro SP/XC (v .212 or newer firmware) and PowerScout™ 3 and 24 (v. 3.16 or newer firmware) rated for 5-5000A. Meters with earlier firmware versions rated from 50-5000A AC.
PowerScout™18 rated for 50-3500A.
**Installed using best practices with conductor centered in the CT window and ensure any external conductors are a minimum distance of > 2X the diameter of the RoCoil. Accuracy below:
20A rated at 1.5% +/- 0.5A when used with DENT ELITEpro/PowerScout meters. RoCoil have been 100% verified to meet the C57.13-2008 Class 1.2 Standard.