The A8332-8F2D Flex I/O Module provides a convenient way to bring data from up to 8 industry standard meters and sensors into facility management/monitoring systems.
As a standalone module, the A8332-8F2D (Flex I/O Module) can be incorporated to any new or existing Modbus Network (BAS, EMS, etc). By using the Windows based Obvius Configuration Console (OCC), users can select input types (pulse, analog, resistive, etc.) and verify communication and wiring. The Flex I/O Module is a quick and cost-effective way to aggregate data from multiple device types and bring that data into any Modbus system.
Applications:
- Load aggregation for Demand Response
- Cost Allocation
- Measurement & verification of energy savings
- Easily add meters & sensors to any Modbus network
- Monitoring performance of building systems including photovoltaic production
The Bad:
The Bottom Line:
Full Review
- 8 user selectable inputs to aggregate pulse, analog, and resistive meters/sensors
- Non-volatile memory retains configuration and pulse counts
- 2 digital outpus
- Digital outputs can be linked with pulse inputs for pulse splitting appliacations
- LED indicators allow visual verification of communication status/signal
- Din rail mounting for quick installation
LEDs 8x input status LEDs (red), 2x Modbus TX/RX (yellow), 1 power/alive status (green)
Memory Pulse count and runtime values are stored in non-volatile memory
Power
Power Supply 24VDC, 200mA but not to exceed 8A, Required (not included)
Communication
Protocols Modbus/RTU
Inputs
Voltage Mode 0-10VDC (min/max/average/instantaneous data) Accuracy: +/- 0.25% of full scale at 20C
Current Mode 4/20mA (min/max/average/instantaneous data) Accuracy +/- 0.25% of full scale at 20C
Resistance Mode 100 ohms to 100k (see installation for accuracy specification)
Pulse Mode
- Intended for use with dry contact outputs (consumption/rate/runtime/status)
- Standard and KYZ modes for form A and C relay outputs
- Input terminals supplies 5V at 5mA sense voltage to detect contact closures
- Maximum rate: 10Hz, minimum pulse width 50ms
- Adjustable contact closure threshold: 100Ω to 5kΩ, broken wire sense above 10kΩ optional
I/O 8 Flex IO inputs with user selectable modes: voltage, current, resistance, pulse and status
Isolation Pulse outputs and RS485 port are isolated to 1500VDC;
Power input, RS232 and analog/pulse inputs are non-isolated
Outputs
Relays 2x, dry contact (opto-fet) 30 VDC, 150 mA max
Physical
Weight 3.7oz (105g)
Size 4.13" x 3.39" x 1.18" (105mm x 86mm x 30mm)
Environment
North America −30 to 70C, 0-95% RH, non-condensing
Altitude 2000M max
Pollution Degree 2
Codes and Standards
Emissions FCC CFR 47 Part 15, Class A, EN 61000, EN 61326
Safety UL61010 Recognized, EN61010
Additional Notes
NEMA enclosures available upon request.
For use with any Modbus RTU device / server