Home » IMS 2000R Series Meter with Outdoor Weatherproof Enclosure
IMS 2000R Series Meter with Outdoor Weatherproof Enclosure




The IMS Series 2000R kWh
meter is designed for industrial and commercial applications,
this UL Listed
Three Phase 4-wire revenue grade kilowatt-hour kWh meter is an
excellent low-cost option. It features a large LCD display, pulse
outputs, an RS-485 serial port, and a ten-year warranty.
Recommendations:
IMS recommends solid core Current Transformers (CT's) for revenue grade billing. Our 100A & 200A color coded CT's assist with correct installation by indicating phase monitored. Also, split core CT's are available for applications where power cannot be interrupted during installation. Our 100A, 200A, and 400A split core models offer 1% accuracy. All IMS 100A and 200A solid core and 100A, 200A, 400A split core CT's have built in open circuit protection that prevents high voltage from appearing on secondary leads if wires become disconnected while CT is under load.
Technical
Recommendations:
IMS recommends solid core Current Transformers (CT's) for revenue grade billing. Our 100A & 200A color coded CT's assist with correct installation by indicating phase monitored. Also, split core CT's are available for applications where power cannot be interrupted during installation. Our 100A, 200A, and 400A split core models offer 1% accuracy. All IMS 100A and 200A solid core and 100A, 200A, 400A split core CT's have built in open circuit protection that prevents high voltage from appearing on secondary leads if wires become disconnected while CT is under load.
Technical
- 3PH 4W Y, 120/208V or 277/480V
- Standard current ratings are 100A, 200A, 400A, 600A, 800A, 1000A, & 1200A (Higher current ratings available on request)
- 1% accuracy; meets all relevant specifications of ANSI C12.1 Code for Electricity Metering when installed with IMS solid core current transformers
- kWh only or kWh & Demand; demand function only available on indoor steel models (See manual for details on the demand functions)
The Good:
The Bad:
The Bottom Line:
The Bad:
The Bottom Line:
Full Review
- 3PH 4W Y, 120/208V or 277/480V
- Standard current ratings are 100A, 200A, 400A, 600A, 800A, 1000A, & 1200A (Higher current ratings available on request)
- 1% accuracy; meets all relevant specifications of ANSI C12.1 Code for Electricity Metering when installed with IMS solid core current transformers
- kWh only or kWh & Demand; demand function only available on indoor steel models (See manual for details on the demand functions)
| Input
Configurations | 3 Phase, 4 Wire
Grounded Delta (120/208 V) | 3 Phase, 4
Wire Wye (120/208, 277/480 or 347/600 V) |
| Supply Voltage Range (Line to Neutral) | Line 1 and Line
2: 102-138 VAC Line 3: 175-240 VAC | 102-138
VAC 235-320 VAC 295-400 VAC |
| Maximum
Input Power | 7 VA | 7 VA |
| Maximum
Rated Current * | Primary:
Max. Operating Current + 10% Secondary: 0.12 A | Primary: Max. Operating Current + 10% Secondary: 0.12 A |
| Line Frequency | 50-60 Hz | 50-60 Hz |
| Power Factor Range | 0.5 to 1.0 leading or lagging | 0.5 to 1.0 leading or lagging |
| Accuracy1 | +/- 0.5% of registration @ 1.0pf, 1% to 100% of
rated current +/- 0.75% of registration @0.5pf, 1% to 100% of rated current | +/- 0.5% of registration @ 1.0pf, 1% to 100% of
rated current +/- 0.75% of registration @0.5pf, 1% to 100% of rated current |
| Meter Operating
Temperature | -30 to +60 degrees C | -30 to +60 degrees C |
| Display Operating Temperature | -20 to +50
degrees C | -20 to +50 degrees C |
| Rated
Pollution Degree2 | 2 | 2 |
| Rated Relative Humidity | 80% | 80% |
| Terminal Blocks: Voltage Terminal: Molex 386344304 or equiv. CT and I/O Terminal: Dinkle/International Connector EK508-11P or equiv. | 12 in-lb of torque maximum 4.4 in-lb of torque maximum | 12 in-lb of torque maximum 4.4 in-lb of torque maximum |
1 Accuracy based on IMS solid core transformers (included), with 100 mA secondary output. Meter input burden resistance at 2 Ohms.
2 Pollution Degree 2: Normally only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
Product brochures
Miscellaneous
Product manuals
No user reviews available.