The AcquiSuite brings "plug and play" capability to the data acquisition market, dramatically reducing the time and training to put a typical building on line. In most applications, the installation can be done by the building engineer or contractor in less than 2 hours. The system automatically detects and configures Modbus devices in just seconds reducing installation time and cost. Because the AcquiSuite automatically detects modbus devices, the installer does not need to enter modbus point numbers or multipliers and thereby reduces configuration errors.
After installation, data from the connected modbus devices is time stamped and stored in non volatile memory at user selected intervals. This interval data is stored at the local site until the next scheduled upload to the SQL database server. Using the built-in modem or Ethernet port, data is sent via ether the network or phone lines to the Building Manager Online server, or collected by your own data warehousing system. From the Building Manager Online website, you can view past data, plot charts, and export data for use on your own PC. Remote configuration is also provided at the BMO website to allow administration of AcquiSuite devices that are on intermittent or shared dialup telephone lines.
The A8812-1 version of the AcquiSuite has 8 flex io inputs built in to the unit. Each input can measure analog sensors (4-20mA or 0-10V) as well as pulse output devices. This simplifies installation for basic projects such as utility meter pulse counting. This version also provides a convenient wall mount design for ease of installation near your power distribution panels.
After installation, data from the connected modbus devices is time stamped and stored in non volatile memory at user selected intervals. This interval data is stored at the local site until the next scheduled upload to the SQL database server. Using the built-in modem or Ethernet port, data is sent via ether the network or phone lines to the Building Manager Online server, or collected by your own data warehousing system. From the Building Manager Online website, you can view past data, plot charts, and export data for use on your own PC. Remote configuration is also provided at the BMO website to allow administration of AcquiSuite devices that are on intermittent or shared dialup telephone lines.
The A8812-1 version of the AcquiSuite has 8 flex io inputs built in to the unit. Each input can measure analog sensors (4-20mA or 0-10V) as well as pulse output devices. This simplifies installation for basic projects such as utility meter pulse counting. This version also provides a convenient wall mount design for ease of installation near your power distribution panels.
Applications:
- Send Meter Data to virtually any software
- Instant integration with industry leading Energy Management/Monitoring Software providers
- Electric, gas, water, steam, renewable, environmental monitoring
- Scalability - Up to 60 modbus devices, or up to 736 Pulse meters with expansion modules
- ModHopper, Flex I/O, SCM supported devices
- AcquiSuite included with meters
- ModHopper wireless diagnostics & troublshooting included with AcquisSuite user interface
- Enertrax DL as free excel software
The Good:
The Bad:
The Bottom Line:
The Bad:
The Bottom Line:
Full Review
| Specifications | |
| Processor | ARM9 embedded CPU, ARM7 IO co-processor |
| Memory | 32 MB RAM |
| Flash ROM | 16 MB NOR Flash (expandable with USB memory device) |
| Interval Recording | 1 to 60 minutes, user selectable |
| LEDs | 8x input, 4 modem activity, Modbus TX/RX, power, system, IO status |
| Console | 2 x 16 LCD character, two push buttons |
| Power | |
| North America | 110-120VAC, 60Hz, primary |
| CE/Europe | 100-240VAC, 50-60Hz, primary (interchangeable plug adapters optional) |
| Power Supply | 24VDC, 1A, class 2 wall brick transformer included |
| Communication | |
| Protocols | Modbus/RTU, Modbus/TCP, TCP/IP, PPP, HTTP/HTML, FTP, NTP, XML, SNMP-Trap |
| LAN | RJ45 10/100 Ethernet, full half duplex, auto polarity |
| Modem | V.34 bis, 33,600 bps |
| USB | USB expansion port |
| Inputs | |
| Serial Port | RS-485 Modbus, supports up to 32 external devices (expandable) |
| I/O | 8x Flex IO inputs with user selectable modes: voltage, current, resistance, pulse and status |
| Outputs | |
| Relays | 2x, dry contact 30 VDC, 150 mA max |
| Physical | |
| Weight | 5lbs (2.3kg) |
| Size | 8" x 9.25" x 2.5" (203mm xx 235mm x 64mm) |
| Environment | |
| North America | 0 to 50C, 0-90% RH, non-condensing |
| CE/Europe | 5 to 40C, 0-90% RH, non-condensing |
| Codes and Standards | |
| FCC CFR 47 Part 15, Class A, EN 61000, EN 61326, CE | |
| Additional Notes | |
| NEMA enclosures available upon request | |
| Manufactured in the USA | |
| 2 Year Warranty | |