HVAC Applications
- Check current draw in motors and compressors.
- Use MAX/MIN/Rescording in the temperature mode to assess efficiency.
- Test run/start capacitors.
- Confirm low voltage control signals.
- Measure flame safeguard device current draw.
- Confirm power sources.
- Analyze temperature and voltage or current data with the aid of the time stamp.
- Insulation test up to 100M Ω.
Electrical Applications
- Check for energized circuits and balance loads.
- 1 Φ /3 Φ (3P3W/3P4W)Power analyzer.
- Evaluate electrical contacts.
- Capture motor in-rush current readings.
- Determine peak power demand periods.
- Verify line voltage stability.
- Monitor motors and other loads for excess heat.
- Check motor run/start capacitor values.
What's Included:
- 9V battery
- Carrying Case
- Manual
AC Voltage (50Hz to 400 Hz):Trms |
Range |
Resolution |
Accuracy |
Sensitivity |
Overload Protection |
999.99 mV |
0.1mV |
±1% ± 0dgts(50,60Hz)
±2%±20dgts(40~100Hz) |
2.0mV |
600V |
9.999 V |
1mV |
0.020V |
99.99V |
10mV |
±1% ± 20dgts(50,60Hz)
±2% ±20dgts(40~400Hz) |
0.20V |
600.0V |
100mV |
2V |
|
Range |
Resolution |
Accuracy |
Sensitivity |
Overload Protection |
999.99 mV |
0.1mV |
±1.0% ± 20dgts |
2.0mV |
600V |
9.999 V |
1mV |
0.020V |
99.99V |
10mV |
0.20V |
600.0V |
100mV |
2V |
|
|
Resistance (Continuity <40 Ω on the 999.9Ω range) |
Range |
Resolution |
Accuracy |
Overload Protection |
999.99 Ω |
100mΩ |
1% ± 10dgts |
600V |
9.999KΩ |
1Ω |
99.99KΩ |
10Ω |
600.0KΩ |
100Ω |
|
Range |
Resolution |
Accuracy |
Overload Protection |
9.999 MΩ |
1KΩ |
5% ± 10dgts |
600V |
99.99 MΩ |
10KΩ |
|
|
1 Φ/3 Φ Phase Angle:(50Hz,60Hz) |
Range |
Resolution |
Accuracy |
Overload Protection |
-60 ° ~ 0 ° ~ +60 ° |
0.1 ° |
±6.0 ° |
ACV >100V,ACA>1 |
|
|
1 Φ/3 Φ KW/hp TRUE Power : (PF>0.5 or Φ<60 °)(1hp=745.7W) |
Range |
Resolution |
Accuracy |
Overload Protection |
60.00KW(<100A) |
10W |
± 5 %rdg ± 20dgts(50,60Hz) |
600VAC/1000AAC |
600.0KW(>100A) |
100W |
|
Range |
Resolution |
Accuracy |
Overload Protection |
40Hz/1KHz |
0.1 Hz |
± 0.5 %rdg ±2dgts |
ACV >0.2V,ACA>6A |
|
|
AC Current(50 Hz to 400Hz):Trms |
Range |
Resolution |
Accuracy |
Sensitivity |
Overload Protection |
99.99A |
10mA |
±2%±20dgts(50,60Hz)
± 4% ± 20dgts (40~400Hz) |
0.10A |
1000A |
999.9A |
100mA |
1.0A |
|
|
μ A Trms:(AC+DC)(Burden Voltage:5mV/ μA) |
Range |
Resolution |
Accuracy |
Sensitivity |
Overload Protection |
99.99 μ A |
10nA |
±1% ± 20dgts |
0.20 μ A |
600V |
999.9 μ A |
100nA |
2.0 μ A |
|
Range |
Resolution |
Accuracy |
Overload Protection |
10.000 μF |
1nF |
1.5% ± 5dgts |
600V |
100.00 μF |
10nF |
100.0 μF |
100nF |
7000 μF |
1 μF |
2.5%±1 5dgts |
|
|
Temperature(K-Type ther mocouple): |
Range |
Resolution |
Accuracy |
Overload Protection |
-50 ℃ to 900 ℃ |
0.1 ℃ |
1% ± 1 ℃ |
30VAC or 60VDC |
-58 ℉ to 1000 ℉ |
0.1 ℉ |
1%±2 ℉ |
|
Range |
Resolution |
Accuracy |
Overload Protection |
2.000V |
1mV |
±2%±1dgts |
600V |
|
Range |
Resolution |
Accuracy |
Overload Protection |
60.00KVA(<100A) |
10VA |
± 2.5 %rdg ± 20dgts |
600VAC/1000AAC |
600.0KVA(>100A) |
100VA | |