Home » Veris H8238 Multi-Circuit Power Monitor
Veris H8238 Multi-Circuit Power Monitor




solution for monitoring multiple electrical services which share a common voltage source. It accepts up to twenty-four industry standard 5A CT inputs and is easily configured for monitoring eight 3Ø, (or six 3Ø plus neutral current) electrical services.
In addition to energy and power, the H8238 also reports diagnostic information
such as power factor, volts, amps, and kVAR, over an RS-485 network using
the industry standard Modbus communication protocol. To protect valuable
equipment, it has built-in alarm registers for over/under voltage, current
and kVA.
The monitoring capabilities and open systems compatibility of the H8238 make it the ideal power monitoring solution for OEM and tenant submtering applications where multiple panelboards are fed from the same power transformer, and for load management of power distribution units commonly used in internet data centers.
The H8238 is a UL508 open type device without enclosure.
Applicatons
- Tenant submetering
- Real-time power monitoring
- Activity based costing
- Load management
Different Models
- V8238 - 8 Channels, MODBUS, 120VAC Supply voltage
- V8238E - 8 Channels, MODBUS, 240VAC Supply voltage
- V8238EL - 8 Channels, MODBUS, 240VAC Supply voltage, Lo Baud
The Bad:
The Bottom Line:
Full Review
- Save labor and installation costs by monitoring up to eight 3Ø, (or six 3Ø plus neutral current) loads from a single service with common voltage connections
- Eliminates the need to install multiple transducers- fewer components to install… saves time and space
- Easy connnection to industry standard fi ve amp CTs
- Improve monitoring system efficiencies by accessing 26 data points per circuit, plus alarms, with one RS-485 drop
- Daisy chain up to 30 units on a single drop...easy wiring
- Field-selectable address, baud rate, parity and wiring connections...simple configuration
|
Electrical Services |
Up to eight 3Ø circuits. All
circuits must share a common line voltage source |
|
Sample Rate |
1280Hz |
|
Operating
|
0 to 60°C (<95%RH, non-con dens
ing) |
|
|
-40°C to 70°C |
|
Accuracy |
±1% (exclusive of user-supplied
CTs)* |
|
Variable Update Rate |
200msec for voltages, 1.6secs for
all other |
|
Measured Voltage Inputs: Number of Channels |
Three or four, dependent on
application |
|
Maximum Voltage |
480VAC+10% = 528VAC |
|
Frequency |
60Hz. |
|
Termination |
4-position cage-clamp terminal
block (max wire size 12 AWG) |
|
Measured Current Inputs: Number of Channels |
24 (8 meters x 3 phases/meter) |
|
CT Input Type |
5 Amp (customer supplied) |
|
CT Range |
Each of eight meters independently
confi gurable from 1A:5A to 9999A:5A |
|
Termination |
6 position cage-clamp terminal
blocks (max wire size 12 gauge) for each
meter |
|
Operating Power Inputs: Power Source |
Dedicated 120VAC line-to-neutral |
|
Power Voltage Tolerance |
+10/-25 % (90-132VAC); (180-264VAC
for H8238E) |
|
Frequency |
60Hz. |
|
Termination |
2-position cage-clamp terminal
block (max wire size 12 AWG) |
|
Network Communications: Type |
|
|
Connection |
DIP-switch selectable 2-wire or
4-wire |
|
Address |
DIP-switch selectable base address
(1 to 233 in steps of 8) |
|
Baud Rate |
DIP-switch selectable 2400, 4800,
9600, or 19200 |
|
Parity |
DIP-switch selectable NONE/ODD/EVEN |
|
Communication Format |
8 data-bits, 1 start-bit, 1
stop-bit |
|
Termination |
5-position pluggable connector |
|
Size |
6.75” x 12.625" x 3.0"
(172x321x76mm) |