Veris H8036 Enercept Enhanced Networked Power Meter

Configure Your Product:

Configuration
VS H8036


Price: From $1,060.94

Quantity
Request a Quote
Ask an Expert



Enercept H8036 Series enhanced data stream meters are networked power meters used for enhanced energy services metering/submetering in commercial and industrial applications. H8036 meters report 26 critical 3-phase power system performance variables.

These innovative meters combine the power metering electronics and high-quality industrial grade CTs in a single package which can be mounted directly inside an electrical panel to substantially reduce installed cost.

In addition, up to 63 H8036 meters can be daisy-chained together on a single RS485 network.

The H8036 is available with a wide range of current sensors from 100A to 2400A, with either 2, 3 or 4 current transformers.

Note: The H8036 measures 26 different electrical, power and energy parameters. If you only require kW and kWh, consider the H8035 Enercept Networked Power Meter.
The Good:


The Bad:


The Bottom Line:

Full Review

The world’s most cost-effective meter
  • Monitor electrical, power & energy parameters (kW, kWh, kVAR, PF, Amps, Volts, etc) at up to 63 locations on a single RS-485 network…greatly reduces wiring time and cost
  • Fast split-core installation eliminates the need to remove conductors
  • Precision metering electronics and current transformers in a single package–reduces the number of installed components– huge labor savings
  • Smart electronics eliminate CT orientation concerns–fast trouble-free in stallation
High accuracy
  • ±1% total system accuracy, (10% to 100% of CT rating)
H8035/6 SERIES SPECIFICATIONS

Input Primary Voltage

208 to 480VAC rms

Number of Phases Monitored

One or Three

Frequency

50/60 Hz

Maximum Primary Current

Up to 2400 amps cont. per phase

Internal Isolation

2000VAC rms

Insulation Class

600VAC rms

Temperature Range

0 to 60°C, 50°C for 2400A

Humidity Range

0 - 95% non-con dens ing

Systems Accuracy

±1% of reading from 10% to 100% of the rated current of the CTs... accomplished by matching the CTs with a meter and calibrating them as a system

Output Physical Characteristics

RS-485, 2 wire plus shield

Baud Rate

9600, 8N1 format

Protocol

Modbus RTU

Current Transformer

Split-core, 100, 300, 400, 800, 1600, 2400 amps


H8036 Data Output Specifications
Data output:           

kWh, Consumption               

kW, Real Power

kVAR, Reactive power         

kVA, Apparent power

Power factor                        

Average Real power

Minimum Real power           

Maximum Real power

Voltage, line to line               

Voltage, line to neutral

Amps, Average current         

kW, Real power ØA

kW, Real power ØB            

kW, Real power ØC

Power factor ØA                 

Power factor ØB

Power factor ØC                 

Voltage, ØA to ØB

Voltage, ØB to ØC              

Voltage, ØA to ØC

Voltage, ØA to Neutral        

Voltage, ØB to Neutral

Voltage, ØC to Neutral        

Amps, Current ØA

Amps, Current ØB              

Amps, Current ØC