Home » Current Transformers » Split Core Current Transformers » Veris H8035 Enercept Networked kW/kWh Meter
Veris H8035 Enercept Networked kW/kWh Meter




These innovative meters combine the power metering electronics and high-quality industrial grade CTs in a single package which can be mounted directly inside an electrical panel to substantially reduce installed cost.
In addition, up to 63 H8035 meters can be daisy-chained together on a single RS485 network.
The H8035 is available with a wide range of current sensors from 100A to 2400A, with either 2, 3 or 4 current transformers.
NOTE: The H8035 Enercept measures kW and kWh only. For additional power, energy and electrical measurement parameters, check out the H8036 Enercept Power Meter.
Applications
- Energy management & performance contracting
- Submetering for commercial tenants
- Activity based costing in commercial and industrial facilities
- Real-time power monitoring
The Bad:
The Bottom Line:
Full Review
- Monitor power parameters (kW, kWh) at up to 63 locations on a single RS-485 network…greatly reduces wiring time and cost
- Fast split-core installation eliminates the need to remove conductors
- Precision metering electronics and current transformers in a single package–reduces the number of installed components– huge labor savings
- Smart electronics eliminate CT orientation concerns–fast trouble-free in stallation
- ±1% total system accuracy, (10% to 100% of CT rating)
|
Input Primary Voltage |
208
to 480VAC rms |
|
Number of Phases Monitored |
One or Three |
|
Frequency |
50/60 Hz |
|
Maximum Primary Current |
Up to 2400 amps cont. per phase |
|
Internal Isolation |
2000VAC rms |
|
Insulation Class |
600VAC rms |
|
|
0 to 60°C, 50°C for 2400A |
|
|
0 - 95% non-con dens ing |
|
Systems Accuracy ±1% of reading from 10% to 100% of
the rated current of the CTs... accomplished by matching the CTs with a meter
and calibrating them as a system |
|
|
Output Physical Characteristics |
RS-485, 2 wire plus shield |
|
Baud Rate |
9600, 8N1 format |
|
Protocol |
Modbus RTU |
|
Current Transformer |
Split-core, 100, 300, 400, 800,
1600, 2400 amps |