Home » Wireless Sub-Meters » Veris H704-42 Modbus Solid-Core Branch Circuit Monitor, 42 circuits (3/4")
Veris H704-42 Modbus Solid-Core Branch Circuit Monitor, 42 circuits (3/4")




The H704 uses banks of solid-core mini-CTs to monitor the individual circuits in a panelboard. Accumulated information can be transmitted across an RS-485 network to a Modbus host and/or viewed on an optional local display (H8936). Data updates occur about once per second to provide timely maintenance information. As a circuit approaches capacity, warning and alarm levels trigger to warn of the need for intervention to prevent unexpected breaker trips and costly downtime.
APPLICATIONS
- Load based cost allocation
- Overload protection
- Load management
- Load balancing
- Lighting circuits
The Bad:
The Bottom Line:
Full Review
- Up to 63 H704s can be networked on one Modbus RS-485 drop… simplifi ed wiring
- A H704-42 reports current consumed on each circuit in the panel board...one product covers multiple points
- 3/4 or 1 inch on center current sensors accomodate standard breakers...easy installation
- Provides Modbus registers for current limit warnings and alarms...prevents breaker trips
- Integrates with available network display for local indication

Technical Specifications :
|
General: Operating Temp. Range |
0 to 60°C
(<95%RH, non-condensing) |
||
|
Storage Temp. Range |
-40°C to
70°C |
||
|
Power Source |
120VAC
(+10/-25%) line-to-neutral, 50/60Hz. (240VAC for H704-42E/ H704-42/1E) |
||
|
Measured
Current Inputs: Number of Channels |
42 |
||
|
Frequency |
50/60Hz. |
||
|
Sample Frequency |
1280Hz. |
||
|
Update Rate |
1.2 sec |
||
|
Accuracy |
±5% of reading from 5A to 50A |
||
|
Overload Capability |
≤50A 10kAIC breaker curve |
||
|
Connection to Conductor |
Solid-core toroid |
||
|
Network
Communications: Type |
Modbus® RTU |
||
|
Connection |
DIP-switch
selectable 2-wire or 4-wire |
||
|
Address |
DIP-switch
selectable address 1 to 247 |
||
|
Baud Rate |
DIP-switch
selectable 2400, 4800, 9600, 19200 |
||
|
Parity |
DIP-switch selectable NONE, ODD,
EVEN |
||
|
Communication Format |
8
data-bits, 1 start-bit, 1 stop-bit |
||
|
Termination |
5-position
pluggable connector; ( |
||
|
Defaults: Warning Register |
60% of
current sensor rating (confi gurable) |
||
|
Alarm Register |
70% of
current sensor rating (confi gurable) |
||
|
Current Setting |
20 Amp |
||
|
Dimensions Cir. Board Only: |
H704-42 |
H704-42/1 |
|
|
CT Strips…(L x W) |
19.5" (241mm) x 1.0"
(26mm) |
24.0" (607mm) x 1.0"
(25mm) |
|
|
Mainboard…(L x W) |
7.25" (184mm) x 5.75"
(146mm) |
7.25" (184mm) x 5.75"
(146mm) |
|
|
Brackets
Only: CT
Strips…(L x W) |
20.31" (516mm) x 0.75"
(19mm) |
25.06" (639mm) x 0.75"
(19mm) |
|
|
Sensor Spacing |
0.75" (19mm) on center
1.0" (25mm) on center |
|
|