Home » EIG Shark 100T Revenue Grade Power & Energy Transducer
EIG Shark 100T Revenue Grade Power & Energy Transducer
Yes! It ships today. 6 hours to order
Yes! It ships for free.
Yes! Next day delivery available.




The unit utilizes high speed DSP technology with high resolution A/D conversion to provide revenue certifiable accuracy for Utility Billing, Substation Metering, Sub-metering and Critical Metering applications.
Ordering Options

The Shark 100 was engineered to be as easy to use and install as possible. From user interface to mechanical construction, many hours were spent to make the Shark straightforward and intuitive so an installer with minimal meter experience and training can succeed with the product. Shark is programmed using a PDA, a PC Computer or through a simple keypad interface. By using the PC or PDA, a technician or electrician can see a visual phasor diagram of the vectors insuring that CT and Voltage polarities are correct. All inputs are color coordinated and have clear simple to understand labeling to avoid cross wiring mistakes.
There are also two communications ports available on the Shark100 - One port provides RS485 communication speaking Modbus ASCII or Modbus RTU protocol.
(9600 - 57,600 baud) and a second IrDA port is available for remote setup, polling and reading. DNP 3.0 protocol is also included with V-Switch packages V3 and V4. (See the 'features' or 'configure' tab for details of V-Switch package options.)
Applications
- Utility Energy Billing
- Substations Panels
- Power Generation
- Sub-Metering
- Commercial Metering
- Industrial Metering
- Campus Metering
- Analog Meter Replacement
- Original Equipment Power Metering
Measurement Options
The Shark 100 is equipped with EIG’s exclusive V-Switch® Technology. V-Switch®, virtual switch technology allows users, OEMs or Power Utilities to minimize different levels of meters and reduce stocking to one type of hardware. As such V-Switch measurement options can be selected at time of purchase.- V-Switch 1 – Volts and Amps Meter – Default
- V-Switch 2 – Volts, Amps, kW, kVAR, PF, kVA, Freq.
- V-Switch 3 – Volts, Amps, kW, kVAR, PF, kVA, Freq., kWh, kVAh, kVARh and DNP 3.0
- V-Switch 4 – Volts, Amps, kW, kVAR, PF, kVA, Freq., kWh, kVAh, kVARh, %THD Monitoring, Limit Exceeded Alarms and DNP 3.0
The Bad:
The Bottom Line:
Full Review
Electro Industries/GaugeTech introduces industry leading metering technology. Designed to address the most demanding applications, the Shark 100 surpasses others providing advanced performance metering in a low cost, compact, panel meter design. Based on an all new platform, this meter significantly outperforms other devices many times its price. This unit is perfect for new metering applications and for a simple replacement to existing analog meters. The unit utilizes high speed DSP technology with high resolution A/D conversion to provide revenue certifiable accuracy for Utility Billing, Substation Metering, Sub-metering and Critical Metering applications. | |||||||||||
| |||||||||||
Accuracy percentage of Voltage L-N, Voltage L-L, and Current is 0.1%. For Watts, Wh, VARs, VARh, VA, Vah, and PF the accuracy is 0.2%. Accuracy for Frequency is 0.01 Hz, %THD is 1%, and for % load bar 1-120% readings. The Shark 100 is a traceable revenue meter, that contains a utility grade test pulse allowing power providers to verify and confirm that the meter is performing to its rated accuracy. | |||||||||||
| Easy to Use and Install The Shark 100 was engineered to be as easy to use and install as possible. From user interface to mechanical construction, many hours were spent to make the Shark straightforward and intuitive so an installer with minimal meter experience and training can succeed with the product. Shark is programmed using a PDA, a PC Computer or through a simple keypad interface. By using the PC or PDA, a technician or electrician can see a visual phasor diagram of the vectors insuring that CT and Voltage polarities are correct. All inputs are color coordinated and have clear simple to understand labeling to avoid cross wiring mistakes. | |||||||||||
| |||||||||||
Advanced Communication Capability with IrDA Interface
| |||||||||||
![]() | |||||||||||
Superior Voltage and Current Inputs
| |||||||||||
![]() | |||||||||||
| Utility Peak Demand Metering The Shark 100 provides user configured fixed window or rolling window demand. This all you to set up the particular utility demand profile. A Fixed window demand is the demand used over a user configured demand period (usually 5, 15 or 30 minutes). A rolling window demand is a fixed window demand that moves for a user specified sub-interval period. An example is would be a 15 minute demand using 3 sub-interval provides a new demand reading every 5 minutes based on the last 15 minutes. Readings for kW, kVAR, kVA and PF are calculated using utility demand features. All other parameters offer max and min capability over the user selectable averaging period. Voltage provides an instantaneous max and min reading displaying the highest surge and lowest sag seen by the meter. | |||||||||||
| |||||||||||
![]() | |||||||||||
0-416 Volts Line To Neutral, 0-721 Volts Line to Line
Universal Voltage Input
Input Withstand Capability – Meets IEEE C37.90.1 (Surge Withstand Capability)
Programmable Voltage Range to Any PT ratio
Supports: 3 Element WYE, 2.5 Element WYE, 2 Element Delta, 4 Wire Delta Systems
Burden: 0.36VA per phase Max at 600V, 0.014VA at 120 Vo l t s
Input wire gauge max (AWG 12 / 2.5mm2 )
N o t e : Accuracy specs doubled for 2.5 Element connections.
Current Inputs
Class 10: (0 to 11) A, 5 Amp Nominal
Class 2: (0 to 2) A, 1A Nominal Secondary
Fault Current Withstand: 100 Amps for 10 Seconds, 300 Amps for 3 Seconds, 500 Amps for 1 Second.
Programmable Current to Any CT Ratio
Burden 0.005VA per phase Max at 11Amps
5mA Pickup Current
Pass through wire gauge dimension: 0.177” / 4.5mm
Isolation
All Inputs and Outputs are galvanically isolated to 2500 Volts AC.
Environmental Rating
Storage: (-40 to +85)° C
Operating: (-30 to +70)° C
Humidity: to 95% RH Non-
Condensing
Faceplate Rating:
NEMA12
(Water Resistant)
Mounting Gasket Included
Sensing Method
True RMS
Sampling at 400+ Samples per Cycle on all channels measured readings simultaneously Harmonic %THD (% of Total Harmonic Distortion)
Update Rate
Watts, VAr and VA-100msec
All other parameters-1second
Power Supply
(90 to 265) Volts AC and (100 to 370) Volts DC. Universal AC/DC Supply
Burden: 10VA max.
Communication Format
2 Com Ports (Back and Face Plate)
RS485 Port (Through Back Plate)
IrDA (Through Faceplate)
Com Port Baud Rate: (9600 to 57,600)
Com Port Address: 0-247
8 Bit, No parity
Modbus RTU, ASCII or DNP 3.0 Protocols
Dimensions and Shipping
Weight: 2 lbs
Basic Unit: H4.85 x W4.82 x L4.25
Shark100 - mounts in 92mm DIN and ANSI C39.1 Round Cut-outs
S h a r k 1 0 0 T-DIN rail mounted transducer
Shipping Container Dimensions: 6” cube
Compliance:
IEC 687 (0.2% Accuracy)
ANSI C12.20 (0.2% Accuracy)
ANSI (IEEE) C37.90.1 Surge Withstand
ANSI C62.41 (Burst)
IEC1000-4-2 – ESD
IEC1000-4-3 – Radiated Immunity
IEC 1000-4-4 – Fast Tr a n s i e n t
IEC 1000-4-5 – Surge Immunity