Fluke i2000 FLEX Flexible AC Current Probe
Downloads:
datasheet



Fluke i2000 FLEX Flexible AC Current Probe

Model: I2000-FLEX

2000A flexible AC current transformer for Fluke power quality analyzers.

$399.99 USD

2 to 3 Weeks

Add In House NIST Traceable Calibration to your I2000-FLEX

Clear selected options



The Fluke i2000flex AC Current Clamp increases the current measurement range of your Fluke digital multimeter.

The Fluke i2000flex is an AC current probe utilizing the Rogowski principle. It can be used to measure currents up to 2000A when used in conjunction with multimeters, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation and measurement of odd-shaped objects without breaking the circuit.

Used in conjunction with multimeters, recorders, data loggers, power quality analyzers, or oscilloscopes.
  • Three ranges: 20A, 200 A & 2000 A, 1 mV, 10 mV or 10 mV/A output
  • Ideal for current measurement on thick and hard to reach conductors without breaking the circuit
  • Maximum conductor diameter 178 mm
  • CAT III 600V safety rating


Electrical specifications
Current ranges 20 A 200 A 2000 A AC rms
Output sensitivity (AC-coupled) 100 mV 10 mV 1 mV 1 mV per A
Load impedance 100 kΩ minimum
Accuracy at +25 °C ± 1 % of range (45 Hz to 65 Hz)
Linearity 10 % to 100 % of range ± 0.2 % of reading
Noise 8 mV ac rms (30 A) 2 mV ac rms (300 A, 3000 A)
Frequency range 10 Hz to 20 kHz (-3 dB)
Phase error < ± 1 ° (45 Hz to 65 Hz) ± 10 ° (at 20 kHz)
Position sensitivity with cable > 25 mm from the coupling ± 2 % of range
External field with cable > 200 mm from the head ± 1 % of range
Power supply 2 x AA/MN 1500/LR6 Alkaline, 200 hours, low battery indicator
Temperature Coefficient ± 0.08% of reading per°C
Working voltage see Safety standards section 600 V AC rms or DC

General Specifications
Head cable length (double insulated)

610 mm (24 in)
Head cable diameter

14.3 mm (0.56 in)
Head bend radius

38.1 mm (1.5 in)
Cable length (head to electronics)

2 m (6.56 ft)
Output connection

Molded 4 mm safety plugs (not integrated)
Operating temperature range

0 °C to +70 °C (32 °F to 158 °F) (head and electronics)
Storage temperature range

-40 °C to +105 °C (-40 °F to 221 °F) (head)

-20 °C to +85 °C (-4 °F to 185 °F) (electronics)
Operating humidity

15 % to 85 % (non-condensing)
Weight

180 g (6.34 oz) (head)

190 g (6.70 oz) (electronics)
Safety standards

EN 61010-1: 2001

EN 61010-2-032: 2002

EN 61010-031: 2002

600 Vrms, Category III, Pollution Degree 2

Use of the probe on uninsulated conductors is limited to 600 V ac rms or dc and frequencies below 1 kHz.
EMC standards

EN 61326: 1998 +A1, A2, & A3
Dimensions
HxWxD 116 mm x 68.5 mm x 30 mm (4.56 in x 2.69 in x 1.18 in)

Click here for complete specifications on the Fluke I2000-FLEX

Ask a question about the Fluke i2000 FLEX Flexible AC Current Probe:

comments powered by Disqus

Review the Fluke i2000 FLEX Flexible AC Current Probe

" data-description="2000A flexible AC current transformer for Fluke power quality analyzers.">